검색하기
KVC as a vacuum measuring instrument specialized company aiming to become a leading company in 21stcentury control and measurement industry
KTM100
KTM 100 / 100 Channel Multi input module |
Specitification | |
---|---|
Dimension | |
Manual |
This is a module that can receive 100 channels of various signals such as pressure, temperature, and flow rate and transmit them to PLC or MMI.
Feature
-TC/mA Type Sensor 100 Channel Signal
-Processed with a high-performance, high-precision 16-bit A/D converter and transmitting measured values to ModBus RTU.
Sensor Calibration
-A function to add or subtract a compensation value for the measured value when the zero point changes due to using the sensor for a long time or when an error occurs due to a long sensor line length.
Before sensor correction = 510℃
After sensor correction = Measured value + Correction value
= 510℃ - 10℃ = 500℃
Display Scaling
-If the input is mV, the input value can be displayed by scaling.
Example) Input is 0~100mV Display 0.0~800.0
IN-H = 100.0 / IN-L = 0.0
SC-H = 8000 / SC-L = 0.0
Installation Precautions
-Do not overtighten the mounting bolts.
-Cannot be used at altitudes above 2000m.
-Be sure to install indoors or in a non-exposed location.
- Please avoid the installation locations below.
Places with corrosive gases, places with heavy dust, places with strong high frequencies, places with moisture, places subject to vibration or heat.
Need help?
Compact an Appcations Specialist by sending email to KVC or Call 032-234-3030
Specification
-INPUT : TC(B,R,S,K,E,J,T,N), 100mV( max 100 Channel)
-Measurement and update cycle: 50ms/100CH
-Accuracy: ±0.2%FS
-CMRR(Common Mode Rejection Ratio) : 140db or more
-NMRR(Normal Mode Rejection Ratio) : 50db ior more
-Built-in moving average filter (1-32)
-ModBus communication output(Option)
method : RS485 / Ethernet
data length : 8bit
Speed : 1200, 2400, 4800, 9600, 19200, 38400, 115200(Rotary switch settings)
Parity : Even Parity
Maximum number of connected units: 10
Protocol : ModBus 1.1 RTU
Insulation Resistance : 100MΩ/1000VDC
-Terms of use
Operating temperature and humidity: -5℃~55℃, 10℃~90℃
Storage temperature and humidity: -20℃~70℃, 5℃~95℃
-Power voltage
Voltage used: DC12~30Volt (within 2000mA)
Power consumption: 5W (MAX)
Insulation resistance: 100mΩ, INPUT(power)-RS485 MoBus
-etc
Weight: 5Kg
Mounting method: wall mounting type